Heat pumps

Do Cold-Climate Heat Pumps Work at -25°C in Ottawa?

Outdoor cold-climate heat pump on a raised stand beside a brick house in deep winter snow

It’s the question we hear most about heat pumps: “Sure, but what about January?” The short answer is that cold-climate models keep running well below -25°C. The longer answer, about how much heat they make that cold and what covers the gap, is what decides whether one is right for your home.

How cold does Ottawa actually get?

Heating systems in Ontario aren’t sized for the coldest night on record. They’re sized for a design temperature set out in the Ontario Building Code’s Supplementary Standard SB-1. It uses the “January 2.5%” value: the temperature that January air is at or above for 97.5% of the hours.

For Ottawa, SB-1 lists a January 2.5% design temperature of -25°C for most of the city (including the airport, City Hall, Kanata and Barrhaven), and -26°C for Orléans. The colder 1% values are -27°C and -28°C. So -25°C isn’t a hypothetical; it’s the number a proper heat-loss calculation for an Ottawa home is built around.

Do heat pumps keep working that cold?

Cold-climate models do. Natural Resources Canada says cold-climate air-source heat pumps can operate at temperatures as low as -30°C, though supplemental heat may be needed below that.

That’s not true of every heat pump. NRCan notes that most air-source heat pumps have a minimum operating temperature, and for newer models it ranges from about -15°C to -25°C. Below that cut-off, a backup system has to carry the house. That’s why the “cold-climate” label, and the specific model, matter so much in Ottawa.

As our heat pump page puts it, modern cold-climate heat pumps work efficiently even in sub-zero temperatures when properly sized and installed.

Running isn’t the same as keeping up

A heat pump pulls heat from outdoor air. As the air gets colder, there’s less heat to pull, so two things fall: capacity (how much heat it delivers) and efficiency (how much heat you get per unit of electricity).

NRCan’s figures show the drop. Air-source heat pumps have a coefficient of performance (COP) of about 2.0 to 5.4 at 8°C, falling to about 1.1 to 3.7 at -8°C. A COP of 2 means two units of heat for every unit of electricity; electric baseboards are 1.

The cold-climate specification used by many efficiency programs, from Northeast Energy Efficiency Partnerships (NEEP), requires a COP of at least 1.75 at -15°C (5°F) at maximum capacity, and variable-speed compressors. NRCan’s sizing guide uses the same idea: a cold-climate heat pump is one that maintains its capacity and COP in the cold.

The NEEP specification itself warns that meeting the spec doesn’t make a unit right for every home. Contractors and homeowners still need to look at the building’s heat loss and the equipment’s capacity at the design temperature.

The balance point: where backup heat comes in

As it gets colder, your house loses heat faster while the heat pump’s output shrinks. NRCan calls the temperature where those two lines cross the thermal balance point. Below it, the heat pump can supply only part of the heat, and something else makes up the rest.

NRCan describes three switch-over settings your installer can choose from:

  • Thermal balance point: the heat pump alone can’t keep up below this temperature.
  • Economic balance point: below this temperature, running the backup (for example, natural gas) costs less than running the heat pump.
  • Cut-off temperature: the heat pump’s minimum operating temperature.

Backup heat comes in two main forms. In an all-electric setup, electric elements in the ductwork or baseboards add heat alongside the heat pump. In a hybrid (dual-fuel) setup, a furnace or boiler takes over below a set temperature. The City of Ottawa describes a common dual-fuel arrangement in which the system switches to the gas furnace below about -12°C.

For a side-by-side look at those choices, see our post on heat pump vs furnace vs hybrid in Ottawa.

What about defrost?

In freezing weather, frost builds up on the outdoor coil. NRCan explains that the heat pump periodically switches into a defrost mode, briefly reversing to melt it, and that supplementary heat may also be needed while it defrosts. Seeing steam rise from the outdoor unit on a cold morning is normal. Ice that keeps building up, or a unit buried in snow, is worth a call.

Sizing makes or breaks it

NRCan stresses that sizing is critical. In Ottawa that comes down to a few questions:

  • What is the home’s heat loss at -25°C? A room-by-room heat-loss calculation, not a guess from square footage or the old furnace label.
  • What does the chosen model deliver at -25°C? Ask for the manufacturer’s cold-temperature capacity data, not just the nameplate rating.
  • What covers the gap below the balance point? Electric backup, your existing furnace, or a new one.
  • Is the ductwork up to it? Ducts that were sized for a furnace may need changes, so it’s worth checking them.
  • Where will the outdoor unit sit? It should be raised above typical snow levels and kept out from under roof drip lines.

Proper sizing starts with a heat-loss calculation for your home, and we can compare a heat pump with a furnace or a hybrid setup for your home.

Rebates and paperwork

Most of the rebate money available to Ottawa homeowners right now is for cold-climate heat pumps, insulation and smart thermostats, not standard furnace or AC replacements. Programs change, and some require pre-approval before installation, so check before you buy. Our rebates page summarizes the programs we could confirm (last checked October 2026), and we help with the paperwork.

Thinking about a heat pump?

Call 613-862-5551 or book online and we’ll talk through your home, your current heating and the options. Once it’s installed, a yearly visit keeps it running well; see our heat pump maintenance page for what we check.

Frequently asked questions

Will a heat pump work at -25°C?

A cold-climate air-source heat pump can. Natural Resources Canada says cold-climate models can operate down to about -30°C. Many standard models stop between about -15°C and -25°C, so the model matters.

Does a heat pump need backup heat in Ottawa?

Usually, yes. Ottawa’s design temperature is about -25°C, and a heat pump’s output drops as it gets colder. Electric backup or a furnace covers the gap below the balance point and can help during defrost.

What is Ottawa’s design temperature for heating?

Ontario’s Supplementary Standard SB-1 lists a January 2.5% design temperature of -25°C for most of Ottawa and -26°C for Orléans.

Is a heat pump efficient in extreme cold?

Efficiency falls as it gets colder. NRCan’s figures show COPs of about 1.1 to 3.7 at -8°C, compared with 2.0 to 5.4 at 8°C. Cold-climate models are designed to hold capacity and efficiency better in the cold.

Why is steam coming off my heat pump in winter?

That’s usually the defrost cycle. The heat pump briefly reverses to melt frost off the outdoor coil, which can release steam. Ice that keeps building up is worth having checked.

Sources

Sources last checked October 2026. Programs, rules and prices change; always confirm on the official website.

Need help? Call 613-862-5551 or book online. Regular hours Mon–Fri 9 AM–5 PM · Emergency service 24/7.